Product Features
1. Automatic start: After the diesel engine pump unit receives the fire alarm/pipe network pressure/power failure/or other start signals, it can automatically start and put into full load operation within 15 seconds;
2. Automatic Charging: the battery can be automatically charged by the commercial power or diesel engine charging motor to ensure the smooth start of the whole unit;
3. Automatic Alarm: automatic alarm protection for low oil pressure, high water temperature and other faults of the diesel engine, and then alarm and shut down when the speed is exceeded;
4. Automatic preheating: making the diesel engine in a heat standby state to ensure emergency work;
5. Direct connection: The diesel engine pump units below 360kw adopt the domestically created direct connection technology between the diesel engine and the water pump through flexible couplings, which reduces the point of failure, greatly shortens the start-up time of the unit, and increases the reliability and emergency performance of the whole unit;
6. The users can also set other alarm output according to different requests (non-standard supply);
7. With remote telemeter, telesignaling and remote control functions (non-standard supply);
8. The equipment is powered by X6135, 12V135, 4102, 4105, 6102 and other series of diesel engines. The diesel engine (with clutch) is connected to the fire pump through a high-elastic coupling to form a fire pump unit. The unit also includes a diesel tank, a cooling water tank, a fan, control panel (for automatic unit) and other components;
9. When it is an automatic control unit, the split diesel engine automatic control cabinet (programmable) realizes the automatic start, input, and automatic switching of the system (the electric pump set is switched to the diesel engine pump set or the diesel engine pump set is switched to another diesel set ), automatic protection (diesel engine over speed, low oil pressure, high water temperature, three start failures, low oil level, low battery voltage, etc. alarm shutdown protection) and other functions. At the same time, it can also interface with the user's fire control center or automatic fire alarm device to achieve remote monitor;
10. In order to ensure the whole unit normal operation in the environment below 5°C, the unit can be attached with an AC220V cooling water preheating device.
11. Diesel engine fire pumps can be combined with electric pump sets, stabilized pumps to form an automatic fire water supply system;
12. There are two types of water intake methods for fire pumps: self-priming and suction. According to the requirements of fire protection regulations, it is generally self-priming water diversion. If the user needs to suck up the water intake system, it should be mentioned when ordering.
Working Conditions
1. Altitude Height: 2500 meters
2. Environment Temperature: -25? - 55??
3. Relative Air Humidity: 9%-95%
4. Earthquake Intensity: 7 degrees
Brand diesel engine You can choose the diesel engine brand according to the requirements
Water tank and cooling fan to ensure cooling efficiency
Energy-efficient pump head Improving work efficiency
Universal Joint Universal joint connection to improve efficiency